| Technical data | KL1862 | KL1872 |
|---|---|---|
| Specification | EN 61131-2, type 1/3 | |
| Number of inputs | 16 | |
| Nominal voltage | 24 V DC (-15 %/+20 %) | |
| “0“ signal voltage | -3…+5 V (EN 61131-2, type 1/3) | |
| “1“ signal voltage | 11…30 V (EN 61131-2, type 3) | |
| “0“ signal current | 0…1.5 mA | |
| “1“ signal current | 2.0…2.5 mA | |
| Input filter | typ. 3.0 ms | typ. 0.2 ms |
| Current consumpt. K-bus | typ. 3 mA | |
| Electrical isolation | 500 V (K-bus/field potential) | |
| Bit width in the process image | 16 inputs | |
| Configuration | no address or configuration setting | |
| Weight | approx. 50 g | |
| Operating/storage temperature | 0…+55 °C/-25…+85 °C | |
| Relative humidity | 95 %, no condensation | |
| Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27/29 | |
| EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 | |
| Protect. class/installation pos. | IP 20/variable | |
| Approvals | CE, UL, Ex | |
| Special terminals | |
|---|---|
| KL1862-0010 | 16-channel digital input 24 V DC, 3.0 ms, flat-ribbon cable connection, switching to ground potential |