| Technical data | KL2114 | KS2114 | KL2134 | KS2134 |
|---|---|---|
| Connection technology | 2-/3-wire | |
| Number of outputs | 4 | |
| Rated load voltage | 24 V DC (-15 %/+20 %) | |
| Load type | ohmic, inductive, lamp load | |
| Max. output current | 0.5 A (short-circuit-proof) per channel | |
| Short circuit current | ≤ 2 A | |
| Breaking energy | ≤ 150 mJ/channel | |
| Reverse voltage protection | – | yes |
| Electrical isolation | 500 V (K-bus/field potential) | |
| Current consumption power contacts | typ. 30 mA + load | |
| Current consumpt. K-bus | typ. 9 mA | |
| Bit width in the process image | 4 outputs | |
| Configuration | no address or configuration setting | |
| Weight | approx. 70 g | |
| Operating/storage temperature | 0…+55 °C/-25…+85 °C | -25…+60 °C/-40…+85 °C |
| Relative humidity | 95 %, no condensation | |
| Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27/29 | |
| EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 | |
| Protect. class/installation pos. | IP 20/variable | |
| Pluggable wiring | for all KSxxxx Bus Terminals | |
| Approvals | CE, UL, Ex | CE, UL, Ex, GL |
|
Product announcement
|
KL2114 and KL2134 with operating temperature 0…+55 °C (storage temperature -25…+85 °C) available; KL2134 with operating temperature -25…+60 °C (storage temperature -40…+85 °C) estimated market release 1st quarter 2012 |