| Technical data | KL4424 | KS4424 | KL4428 | KS4428 |
|---|---|---|
| Technology | single-ended | |
| Number of outputs | 4 | 8 |
| Power supply | 24 V DC via power contacts (alternative 15 V DC with power supply terminal KL9515) | |
| Signal current | 4…20 mA | |
| Load | 350 (short-circuit-proof) | 150 (short-circuit-proof) |
| Output error | ±0. % (relative to end value) | ±0. % (relative to end value) |
| Resolution | 12 bits | |
| Conversion time | ~ 4 ms | ~ 8 ms |
| Electrical isolation | 500 V (K-bus/signal voltage) | |
| Current consumption power contacts | typ. 60 mA + load | |
| Current consumpt. K-bus | typ. 20 mA | |
| Bit width in the process image | output: 4 x 16 bit data (4 x 8 bit control/status optional) | output: 8 x 16 bit data (8 x 8 bit control/status optional) |
| Special features | – | increased packing density |
| Weight | approx. 75 g | |
| Operating/storage temperature | 0…+55 °C/-25…+85 °C | |
| Relative humidity | 95 %, no condensation | |
| Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27/29 | |
| EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 | |
| Protect. class/installation pos. | IP 20/variable | |
| Pluggable wiring | for all KSxxxx Bus Terminals | |
| Approvals | CE, UL, Ex, GL | |