| Technical data | EL3058 | ES3058 |
|---|---|
| Number of inputs | 8 (single-ended) |
| Technology | single-ended |
| Signal current | 4…20 mA |
| Distributed clocks | – |
| Internal resistance | 85 Ω typ. + diode voltage |
| Input filter limit frequency | 1 kHz |
| Conversion time | 1.25 ms default setting, configurable |
| Resolution | 12 bits (16 bits presentation, incl. sign) |
| Measuring error | ≤ ±0.3 % (relative to full scale value) |
| Surge voltage resistance | 30 V max. |
| Electrical isolation | 500 V (E-bus/signal voltage) |
| Current consumption power contacts | – |
| Current consumption E-bus | typ. 130 mA |
| Dielectric strength | max. 30 V |
| Bit width in the process image | inputs: 32 byte |
| Configuration | no address or configuration setting required |
| Special features | standard and compact process image, activatable FIR/IIR filters, limit value monitoring |
| Weight | approx. 60 g |
| Operating/storage temperature | 0…+55 °C/-25…+85 °C |
| Relative humidity | 95 %, no condensation |
| Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27/29 |
| EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
| Protect. class/installation pos. | IP 20/variable |
| Pluggable wiring | for all ESxxxx terminals |
| Approvals | CE, UL, Ex |