| System data | EtherCAT | BK1150 |
|---|---|
| Number of I/O stations | 65,535 |
| Number of I/O points | depending on controller |
| Data transfer medium | Industrial Ethernet cable, screened, min. CAT 5 |
| Max. cable length | 100 m (100BASE-TX) |
| Data transfer rates | 100 Mbaud |
| Data transfer time | typ. 0.01 ms in the case of 10 modules for 32 bit inputs and outputs each (without K-bus run-time) |
| Technical data | BK1150 |
|---|---|
| Number of Bus Terminals | 64 (255 with K-bus extension) |
| Max. number of bytes fieldbus | 1,024 byte input and 1,024 byte output |
| Configuration possibility | via KS2000 or EtherCAT (ADS) |
| Bus interface | 2 x RJ 45 |
| Power supply | 24 V DC (-15 %/+20 %) |
| Input current | 70 mA + (total K-bus current) /4, 500 mA max. |
| Starting current | approx. 2.5 x continuous current |
| Recommended fuse | ≤ 10 A |
| Current supply K-bus | 2,000 mA |
| Power contacts | 24 V DC max./10 A max. |
| Electrical isolation | 500 V (power contact/supply voltage/Ethernet) |
| Distance between stations | 100 m (100BASE-TX) |
| Dimensions (W x H x D) | 44 mm x 100 mm x 68 mm |
| Weight | approx. 110 g |
| Operating/storage temperature | 0…+55 °C/-25…+85 °C |
| Relative humidity | 95 %, no condensation |
| Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27/29 |
| EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
| Protect. class/installation pos. | IP 20/variable |
| Accessories | |
|---|---|
| KS2000 | configuration software for extended parameterisation |
| Cordsets | cordsets and connectors |
| FC90xx-00xx | PC Fieldbus Cards with PCI interface |
| Ordering information | Description |
|---|---|
| BK1150 | EtherCAT “Compact” Bus Coupler for up to 64 Bus Terminals (255 with K-bus extension) |
| BK1120 | EtherCAT “Economy plus” Bus Coupler for up to 64 Bus Terminals (255 with K-bus extension) |
| BK1250 | EtherCAT “Compact“ Coupler between EtherCAT Terminals (E-bus) and Bus Terminals (K-bus), adapter terminal |
| CX8010 | EtherCAT Embedded PC |