| Technical data | EL3773 |
|---|---|
| Number of inputs | 3 x current, 3 x voltage |
| Technology | 3-phase power monitoring for alternating/direct voltages |
| Oversampling factor | n = 1…100 selectable |
| Distributed clocks | yes |
| Input filter limit frequency | 5 kHz (-3 dB) |
| Conversion time | min. 100 µs, all channels simultaneously |
| Measured values | current, voltage |
| Measuring voltage |
max. 500 V AC 3~ (ULx-N: max. 288 V AC) common reference potential |
| Measuring current | max. 3 x 1 Aeff AC/1.5 A DC via measuring transformers x A AC/1 A AC |
| Resolution | 16 bits (incl. sign) |
| Measuring error | ≤ ±0.5 % (relative to full scale value) |
| Electrical isolation | 2,500 V |
| Current consumption power contacts | – |
| Current consumption E-bus | typ. 200 mA |
| Special features | oversampling, software filter activatable, single-phase operation also possible |
| Weight | approx. 75 g |
| Operating/storage temperature | 0…+55 °C/-25…+85 °C |
| Relative humidity | 95 %, no condensation |
| Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27/29 |
| EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
| Protect. class/installation pos. | IP 20/variable |
|